INVT GD350A How to setup Fire Mode

GD350 fire mode | GD350 FAQ


By default, S1 is default as forward; S3 is default as fault reset; we can assign S4 to fire mode; Set Function of S4 terminal [P05.04] to 82; settings of the fire mode are:

Fire mode function [P11.53]

- 0 (Default): Invalid

- 1: Fire mode 1

- 2: Fire mode 2

When P11.53=0, the fire mode is invalid, and the normal running mode is used. In this case, the VFD stops when encountering a fault. When the fire mode function is valid, the VFD runs at the speed specified by P11.54. 

When fire mode 1 is selected, the VFD always runs except when the VFD has been damaged.

When fire mode 2 is selected, the VFD always runs, but the VFD stops when encountering OUT1, OUT2, OUT3, OC1, OC2, OC3, OV1, OV2, OV3, or SPO.

Note: Terminal control must be used for a fire mode. When the fire mode has lasted 5 minutes, it is reset, and no warranty of repair is processed.

Running frequency in fire mode [P11.54] is set to 50Hz by default.

Fire mode flag [P11.55] is the indicator whether the warranty is voided by the fire mode